<?xml version="1.0" encoding="utf-8"?>
<TcPlcObject Version="1.1.0.1" ProductVersion="3.1.4024.12">
<POU Name="FT_PIWL" Id="{8cecf0cc-cac1-4356-93da-bbf6e749af95}" SpecialFunc="None">
<Declaration><![CDATA[FUNCTION_BLOCK FT_PIWL
VAR_INPUT
IN : REAL;
KP : REAL := 1.0;
KI : REAL := 1.0;
LIM_L : REAL := -1.0E38;
LIM_H : REAL := 1.0E38;
RST : BOOL;
END_VAR
VAR_OUTPUT
Y : REAL;
LIM : BOOL;
END_VAR
VAR
init: BOOL;
tx: DWORD;
tc : REAL;
t_last: DWORD;
in_last : REAL;
i: REAL;
p: REAL;
END_VAR
]]></Declaration>
<Implementation>
<ST><![CDATA[(*
version 1.3 11. mar. 2009
programmer hugo
tested by oscat
FT_PIWL is a PI controller.
The PID controller works according to the fomula Y = IN *(KP+ KI * INTEG(e) ).
a rst will reset the integrator to 0
lim_h and Lim_l set the possible output range of the controller.
the output flag lim will signal that the output limits are active.
the integrator ist equipped with anti wind-up circuitry which limits trhe total output ranke to lim_l and lim_h
default values for KP = 1, KI = 1, ILIM_L = -1E37, iLIM_H = +1E38.
*)
(* @END_DECLARATION := '0' *)
(* initialize at power_up *)
IF NOT init OR RST THEN
init := TRUE;
in_last := in;
t_last := T_PLC_US();
i := 0.0;
tc := 0.0;
ELSE
(* read last cycle time in Microseconds *)
tx := T_PLC_US();
tc := DWORD_TO_REAL(tx - t_last);
t_last := tx;
(* calculate proportional part *)
p := KP * IN;
(* run integrator *)
i := (IN + in_last) * 5.0E-7 * KI * tc + i;
in_last := IN;
(* calculate output Y *)
Y := p + i;
(* check output for limits *)
IF Y >= LIM_H THEN
Y := LIM_H;
IF ki <> 0.0 THEN
i := LIM_H - p;
ELSE
i := 0.0;
END_IF;
LIM := TRUE;
ELSIF Y <= LIM_L THEN
Y := LIM_L;
IF ki <> 0.0 THEN
i := LIM_L - p;
ELSE
i := 0.0;
END_IF;
LIM := TRUE;
ELSE
LIM := FALSE;
END_IF;
END_IF;
(* revision history
hm 13. jun. 2008 rev 1.0
original version
hm 27. oct. 2008 rev 1.1
integrator will not be adjusted when ki = 0
hm 25. jan 2009 rev 1.2
module will also work with negative K
hm 11. mar. 2009 rev 1.3
real constants updated to new systax using dot
*)]]></ST>
</Implementation>
<LineIds Name="FT_PIWL">
<LineId Id="26" Count="60" />
<LineId Id="89" Count="12" />
<LineId Id="9" Count="0" />
</LineIds>
</POU>
</TcPlcObject>